TRANBERG® TEF 1058 is a stainless steel junction box for hazardous areas, zone 1, zone 2 and safe area, developed and manufactured at the R. STAHL Tranberg factory in Stavanger. Tranberg has manufactured junction boxes for hazardous areas since the beginning of the Norwegian oil history, and the solutions are developed together with customers to meet the demands for flexibility. The series is certified to both ATEX and IECEx as an Ex eb enclosure, and is used for a wide range of electro, instrument and telecom installations.
Application
- Junction and terminal boxes in hazardous areas, zone 1 and zone 2, and in safe areas
- Electro, instrument and telecom installations offshore, onshore and marine
- Platform for Tranberg heat trace junction boxes, thermostats, small power boxes and control stations, listed as separate products
Features and benefits
- Nine sizes from 05 to 45, empty or with horizontal terminal rail and PE bus bar
- Bright chemical dip or electropolished finish; arctic version with silicone gasket for −60 °C
- Earthing inside on bus bar or terminals, external earth bolt on the right side
- Equipped according to the customer’s component list; only ATEX/IECEx certified glands, blanks and adaptors may be used
- Internal mounting plates and external mounting brackets available for each size
Technical data
| Material housing | Stainless steel AISI 316L / EN 1.4404 |
|---|---|
| Material gasket | EPDM (standard) or silicone (arctic version) |
| Finish | Bright chemical dip or electropolished |
| Ingress protection | IP66 / IP67 |
| Ambient temperature, empty enclosure | −40 °C to +80 °C with EPDM gasket; −60 °C to +135 °C with silicone gasket. Equipped enclosure depends on the internal components. |
| Rated voltage | 750 V |
| Max. conductor | 4 mm² (size 05 and 10), 10 mm² (size 15), 16 mm² (size 20 to 45) |
| Ex protection | II 2 G Ex eb IIC T5 Gb |
Approvals and certificates
- IECEx NEM 14.0001
- PRESAFE 14 ATEX 4124, Directive 2014/34/EU
- EU and UK declarations of conformity; certificates and the user manual are listed above the table
Selecting the right box
Choose the size by the number and cross-section of conductors and the number of cable glands needed; each size datasheet gives the recommended glands per side and the conductor table. Choose the empty box when the box is equipped to a component list, or the version with terminal rail and PE bus bar for standard terminal work. The arctic version has a silicone gasket for ambient temperatures down to −60 °C. Cable glands are found under TEF E204/622, and stopping plugs under TEF 793/650.